电 机 进 水 后 怎 么 处 理

  • 发布日期:2021-07-29 总浏览:



电 机 进 水 后 怎 么 处 理


 电机种类凡多,只要电机进水一般都不会因进水损坏,只是绝缘程度会大大降低。

 不论什么类型电机进水的修理过程大体相似。即拆开电机进行烘干处理。

 今天咱以三相异步电机为例:如果电机被洪水浸泡多日,很可能电机腔内会进入大量泥沙,打开电机抽出转子注意,不要碰到电机绕组,以免造成二次伤害。

 冲剧干净后,首先用万用表1K10K档测其对地绝缘、相间绝缘,这时千万不可以用摇表测量,因为500兆欧的摇表就输出500的直流电压很可能会击穿进水电机的绕组绝缘,造成雪上加霜。

 不论测绝缘高低都下应放弃,丶病马当作好马医。

 进水的电机要进行烘干处理,烘的方法很多,热风机、灯炮、或在夏天的大阳下爆晒、当然用烘箱更好。但温度不可太高,一般恒温保持60度为宜。

 确认烘干后可以用500伏摇表测其对地及相间绝缘,如果对地及相间绝缘都达到0.5兆欧以上电机便可以投入使用,如果低于0.5兆欧就不可以投入使用。

How to deal with the water in the motor

There are many kinds of motors. As long as the motor enters the water, it will not be damaged by the water, but the insulation degree will be greatly reduced.

Regardless of the type of motor, the repair process for water ingress is generally similar. That is, disassemble the motor for drying.

Today, let's take the three-phase asynchronous motor as an example: if the motor is soaked in flood for many days, it is likely that a large amount of sediment will enter the motor cavity. Open the motor and draw out the rotor. Be careful not to touch the motor winding to avoid secondary injury.

After cleaning, first measure the ground insulation and phase to phase insulation with a multimeter at 1K or 10K. At this time, do not use a megger, because a 500 megohm megger will output 500 DC voltage, which is likely to break through the winding insulation of the water inlet motor, making it worse.

No matter how high or low the insulation is measured, you should give up and treat a sick horse as a good horse doctor.

There are many ways to dry the incoming motor, such as hot air blower, light bulb, or explosive drying in the summer sun. Of course, it is better to use an oven. However, the temperature should not be too high. Generally, the constant temperature should be kept at 60.

After confirmation, the insulation to ground and between phases can be measured with a 500 volt megger. If the insulation to ground and between phases reaches more than 0.5 megohm, the motor can be put into use. If it is less than 0.5 megohm, it can not be put into use.

How to deal with the water in the motor

There are many kinds of motors. As long as the motor enters the water, it will not be damaged by the water, but the insulation degree will be greatly reduced.

Regardless of the type of motor, the repair process for water ingress is generally similar. That is, disassemble the motor for drying.

Today, let's take the three-phase asynchronous motor as an example: if the motor is soaked in flood for many days, it is likely that a large amount of sediment will enter the motor cavity. Open the motor and draw out the rotor. Be careful not to touch the motor winding to avoid secondary injury.

After cleaning, first measure the ground insulation and phase to phase insulation with a multimeter at 1K or 10K. At this time, do not use a megger, because a 500 megohm megger will output 500 DC voltage, which is likely to break through the winding insulation of the water inlet motor, making it worse.

No matter how high or low the insulation is measured, you should give up and treat a sick horse as a good horse doctor.

There are many ways to dry the incoming motor, such as hot air blower, light bulb, or explosive drying in the summer sun. Of course, it is better to use an oven. However, the temperature should not be too high. Generally, the constant temperature should be kept at 60.

After confirmation, the insulation to ground and between phases can be measured with a 500 volt megger. If the insulation to ground and between phases reaches more than 0.5 megohm, the motor can be put into use. If it is less than 0.5 megohm, it can not be put into use.